Our large range of wound products start from standard 25VA Control Panel Transformers to 1.5MVA Power Transformers, with a comprehensive offering of products and solutions covering everything in between. The Boardman product range also includes AC Line Reactors and DC Chokes.

UK manufactured control transformer for industrial control panels

Control Circuit Transformers, 50VA – 2.5kVA | MCL Range

The MCL Range covers control circuit transformers from 50VA to 2.5kVA, designed for industrial control panels, machinery, automation systems and electrical control applications.

Manufactured in the UK by Boardman Transformers, the MCL Range offers 230V and 400V supply options with adjustment tappings, making it suitable for applications where dependable control voltage transformation is required.

These control circuit transformers are designed and manufactured to comply with IEC / BS-EN 61558 and include touch-proof terminals, four-hole fixing access and full varnish impregnation to help protect against humidity.

This high quality product is manufactured using automated winding and welding machines; they offer good access to the four-hole fixing, touch-proof terminals and full varnish impregnation to protect against humidity.

Key Features

  • – Control circuit transformer range
  • – Ratings from 50VA to 2.5kVA
  • – Designed for industrial control panels and machinery
  • – 230V and 400V supply options with adjustment tappings
  • – Primary voltage configuration: 15-0-15-230-400V
  • – Secondary voltage options including 12V, 24V, 48V, 110V and 230V
  • – Touch-proof terminals and four-hole fixing access
  • – Full varnish impregnation to help protect against humidity
  • – Designed and manufactured to comply with IEC / BS-EN 61558
  • – UK manufactured by Boardman Transformers

Suitable Applications

The MCL Range is suitable for control circuit applications where reliable voltage transformation and practical installation features are required.

  • – Industrial control panels
  • – Machinery control circuits
  • – Automation systems
  • – Panel builders
  • – OEM electrical assemblies
  • – Manufacturing equipment
  • – Control circuit voltage transformation
  • – Applications requiring 12V, 24V, 48V, 110V or 230V secondary outputs

Control TransformerClass 1 Isolation Transformer with Earth Screen between Primary and Secondary
StandardIEC / BS-EN 61558
Primary Voltages15-0-15-230-400V
Secondary VoltagesOne of the following. 12V, 24V, 48V, 110V, 230V
Frequency50/60Hz
Insulation ClassB
Insulation Resistance> 5 Meg Ω
Dielectric StrengthPrimary to Secondary > 2.5kV Primary to Earth > 2.5kV Secondary to Earth > 2.5kV
Ambient Temperature40

Transformer Circuit Protection

Transformers must be protected against short circuit and overload.

Primary Circuit

The primary side of the Transformer should be protected against short circuit thereby cutting the supply voltage in the event of a short circuit fault. The rating of the primary protection device has to take into account the high inrush current during energizing of the Transformer.

The table below gives suggested protection values to avoid nuisance tripping on inrush:

Rating VAPrimary VoltsAmpsFuseType C MCBType D MCBPrimary VoltsAmpsFuseType C MCBType D MCB
502300.211114150.12500mA11
752300.271114150.15500mA11
1002300.431214150.24111
1502300.652214150.36111
2002300.862624150.48121
2502301.093.15624150.60221
3002301.23.15634150.72222
5002302.1741064151.203.1564
7502303.2661064151.803.1564
10002304.3481064152.40564
15002306.521016104153.616106
20002308.691216104154.8210106
250023010.861625164156.02101610

Secondary Circuit

The secondary circuit should be protected against short circuit and overload.

The value of the protection should be the same or less than the rated output current.

Part No. VAABCDEWeight Kg% Reg.Watts LossInrush VA For 10% Volt dropInrush VA For 5% Volt drop
MCL2566687750440.71164836
MCL5076708656471.19.8910577
MCL7576768656531.58.911135102
MCL10084789564632.18.414250175
MCL150967610284652.256.718375260
MCL200968610284722.85.821550375
MCL2509610110284903.75.627720470
MCL3001208812290734.45.331870585
MCL40012010012290855.35.0301200790
MCL500120120122901066.54.13117001100
MCL750150145140122908.05.26022001475
MCL100015016114012210610.03.36740002500
MCL150015018814012213414.03.28862003850
MCL200019217218016012520.53.310080605030
MCL250019219218016015324.02.6120121007300

Voltage Options and Part Numbers

WindingVoltageCode
Primary15-0-15-230-400V
Secondary0-12VJ
0-24VB
0-48VE
0-110VF
0-230VU

For a 100VA transformer, with an output of 100V, the part number would be MCL100F.

Power Rating Calculation

To choose the size of Transformer required for an application the total inrush VA must be calculated. This figure is then applied to the table above with the maximum allowable voltage drop taken into account. For example, for a calculated inrush of 2,100VA the appropriate transformer is as follows:

  1. For 10% drop in output volts during inrush, choose 750VA
  2. For 5% drop in output volts during inrush, choose 1000VA

Consideration must also be given to the continuous VA requirement.

Related Control Transformer Ranges

If the MCL Range is not the right fit for your application, Boardman Transformers also manufactures other control transformer ranges for different ratings, specifications and compliance requirements.

View the SCL Range for alternative 50VA to 2.5kVA control circuit transformer options.

View the CL Range for larger single phase control and industrial transformer applications

UK manufactured control transformer for industrial control panels

Purchasing

Boardman Transformers’ core range of products are available to purchase through many of the leading UK and international distributors and we are always happy to provide details of where our transformers may be bought.

Should your requirements be of a more specialist or bespoke nature, we ask that you contact us directly to speak to a member of our team.