The C Range covers cCSAus control transformers from 25VA to 5kVA, designed for applications requiring recognised certification for U.S. and Canadian markets.
Manufactured by Boardman Transformers, these control transformers support machinery, panels, OEM equipment and export applications where suitable standards compliance and dependable control voltage transformation are required.
The range includes primary voltage options from 100V to 600V and secondary voltage options from 12V to 600V, with transformers suitable for 50/60Hz applications.
Standards and Compliance
The cCSAus mark indicates that a product has been tested for safety and performance against applicable U.S. and Canadian standards.
Boardman Transformers’ C Range is designed for applications where recognised control transformer compliance is required, including machinery, panels and OEM equipment intended for North American or international use.
- – Canadian and U.S. market applications
- – Suitable for export machinery and panels
- – Applicable standards include C22.2 No. 66.1-06, C22.2 No. 66.0-06, UL5085-1 and UL5085-2
- – Supports applications requiring recognised control transformer certification
Our transformers offer good access to the four-hole fixing, touch-proof terminals and full varnish impregnation to protect against humidity.
Key Features
- – cCSAus control transformer range
- – Ratings from 25VA to 5kVA
- – Designed for U.S. and Canadian market requirements
- – Primary voltage options from 100V to 600V
- – Secondary voltage options from 12V to 600V
- – Suitable for 50/60Hz applications
- – Class 1 isolation transformer with earth screen between primary and secondary
- – Touch-proof terminals and four-hole fixing access
- – Full varnish impregnation to help protect against humidity
- – UK manufactured by Boardman Transformers
Suitable Applications
- – Export machinery
- – Control panels for U.S. and Canadian markets
- – OEM electrical assemblies
- – Industrial automation systems
- – Machinery control circuits
- – International equipment builds
- – Applications requiring cCSAus control transformers
| Control Transformer | Class 1 Isolation Transformer with Earth Screen between Primary and Secondary |
|---|---|
| Standard | C22.2 No. 66.1-06, C22.2 No. 66.0-06, UL5085-1, UL5085-2 |
| Primary Voltages | 100 – 600V |
| Secondary Voltages | 12 – 600V |
| Frequency | 50/60Hz |
| Insulation Class | B |
| VA Ratings | 25VA to 5kVA |
| Dielectric Strength | 250VA or Less 250VA to 5000 VA |
| Winding to winding and winding to core | For 25V Winding 1050V 250V or less 2500V 26V – 250V 1500V 251 – 600V 4000V 251 – 600V 2500V |
| Ambient Temperature | 25℃ |
| VA | A | B | C | D | E | Weight kg |
|---|---|---|---|---|---|---|
| 25 | 66 | 68 | 77 | 50 | 44 | 0.7 |
| 50 | 75 | 70 | 86 | 56 | 47 | 1.1 |
| 63 | 75 | 76 | 86 | 56 | 53 | 1.5 |
| 100 | 84 | 78 | 95 | 64 | 63 | 2.1 |
| 150 | 96 | 86 | 102 | 84 | 72 | 2.8 |
| 200 | 96 | 101 | 102 | 84 | 90 | 3.7 |
| 250 | 120 | 88 | 122 | 90 | 73 | 4.4 |
| 300 | 120 | 100 | 122 | 90 | 85 | 5.3 |
| 400 | 120 | 120 | 122 | 90 | 106 | 6.5 |
| 500 | 150 | 135 | 140 | 122 | 82 | 7.5 |
| 750 | 150 | 161 | 140 | 122 | 106 | 10 |
| 1000 | 150 | 188 | 140 | 122 | 134 | 14 |
| 1500 | 192 | 172 | 180 | 160 | 125 | 20.5 |
| 2000 | 192 | 172 | 180 | 160 | 125 | 20.5 |
| 2500 | 192 | 192 | 180 | 160 | 153 | 24 |
| 3000 | 200 | 130 | 300 | 160 | 110 | 20 |
| 4000 | 200 | 150 | 300 | 160 | 120 | 30 |
| 5000 | 240 | 150 | 390 | 200 | 110 | 40 |
Related Control Transformer Ranges
If the cCSAus C Range is not the right fit for your application, Boardman Transformers also manufactures other control transformer ranges for standard industrial control applications.
View the SCL Range for 50VA to 2.5kVA control circuit transformer applications.
View the MCL Range for alternative 50VA to 2.5kVA control circuit transformer options.
For a wider overview of our control transformer capability, visit our Control Transformers page.